Whether it is the Chongqing Cummins diesel generator set or the Dongfeng Cummins diesel generator set, after long-term operation, phenomena such as aging of the generator set components and excessive fit clearance often occur. These faults should draw great attention from users. This article will conduct relevant analyses and suggestions on how to reduce the occurrence rate of faults and individual typical faults.
Cummins diesel generator set, fault one, low oil pressure
In the running of cummins diesel generator set, low oil pressure will cause poor lubrication unit the transmission parts, if oil removing will appear the phenomenon such as cylinder, cylinder, bearing clearance is too large, directly affect the normal use of cummins diesel generator set.
The low oil pressure of Cummins diesel generator sets is mainly related to the following aspects:
(1) Cooling system: The oil cooler is clogged; The external gap of the radiator core is blocked.
(2) Lubrication system: The oil filter is dirty; The oil suction pipe is blocked. The oil pressure regulator has failed.
(3) Mechanical adjustment and repair; Improper bearing clearance The engine needs a major overhaul. The main bearing or the connecting rod bearing is damaged.
(4) Usage and maintenance: Engine overload; The engine oil should be changed on time and the correct use of the oil filter element should be ensured. Only by following the correct maintenance methods can the normal use of the unit be guaranteed.
Fault 2 of Cummins Diesel Generator Set In the operation of Cummins diesel generator sets, it is common to encounter the situation where the coolant does not circulate. This includes having large circulation but no small circulation, or having small circulation but no large circulation. This leads to rapid increase in cylinder temperature and sudden shutdown due to a rise in oil temperature, directly affecting the safe use of Cummins diesel generator sets.
The reasons for the coolant not circulating are as follows:
(1)The radiator fins of the Cummins diesel generator set are clogged or damaged. If the cooling fan fails to function or the heat sink is clogged, the temperature of the coolant cannot be reduced. If the heat sink is rusted and damaged, it can cause leakage and also lead to poor circulation.
(2) The thermostat of the Cummins diesel generator set is faulty. A thermostat is installed in the engine combustion chamber to control the temperature of the engine combustion chamber. The thermostat must be fully open at the specified temperature (82 degrees) to facilitate small circulation. Without a thermostat, the coolant cannot maintain the circulation temperature, which may cause a low-temperature alarm.
(3)Air mixed in the cooling system of Cummins diesel generator sets causes the pipelines to be blocked. Damage to the suction valve and exhaust valve on the expansion water tank also directly affects the circulation. At this time, it is necessary to frequently check whether their pressure values meet the regulations. The suction pressure is 10kpa and the exhaust pressure is 40kpa. In addition, whether the exhaust pipeline is unobstructed is also an important reason affecting the circulation.
(4)The coolant level of the Cummins diesel generator set is too low or does not meet the regulations. If the liquid level is too low, it can directly cause the coolant temperature to rise, preventing the coolant from circulating. According to regulations, the coolant should be 50% antifreeze +50% softened water +DCA4. If it does not meet the requirements, it will cause pipeline blockage and rust on the inner wall of the pipe, preventing the coolant from circulating normally.
(5)The water pump of the Cummins diesel generator set is faulty. Check whether the water pump is functioning well. If it is found that the transmission gear shaft of the water pump is worn beyond the limit, it indicates that the water pump can no longer function and needs to be replaced to ensure normal circulation.